Update to TIA Standard 942 – Telecommunications Infrastructure Standard for Data Centers

Posted on Posted in New Standards

The major modifications in ANSI/TIA-942-A from ANSI/TIA-942 include:

  • ANSI/TIA-942-A has been harmonized with the TIA-568-C series including the topology, terms, and environmental classifications described in ANSI/TIA-568-C.0, and component specifications in ANSI/TIA-568-C.2 and ANSI/TIA-568-C.3.
  • The content of the addenda – ANSI/TIA-942-1 and ANSI/TIA-942-2 – has been incorporated into this Standard and these two documents will be superseded at the time of publication of ANSI/TIA-942-A.
  • Category 3 and category 5e are no longer recognized for horizontal cabling. Recognized balanced twisted-pair cable types for horizontal cabling are category 6 or category 6A.
  • Recognized multimode optical fiber cable for horizontal and backbone cabling has been changed to OM3 and OM4 850 nm laser-optimized 50/125 m multimode optical fiber cable.
  • The Intermediate Distribution Area (IDA) has been added to the data center topology.
  • Recommendations for energy efficiency have been added.
  • The terms ‘Equipment Outlet’ (EO) and ‘External Network Interface’ (ENI) from ISO/IEC 337 24764 have been added.